Model | HMP-04B |
---|
Suitable for all gaseous and liquid media that will not obstruct the pressure system or attack copper alloy parts. Especially designed for difficult conditions of use, as there are vibrations or quick changes of pressure.
Application: Refrigeration, Air conditioning and Food industry
STANDARD PARAMETERS
Closing: Sealed ring
Mounting: See attached diagrams A , B, C or D
Threaded connection: Ø63: ¼” BSP/NPT; Ø100: ½” BSP/NPT
IP protection: IP65
Accuracy: Class 1.6
Pressure limits:
Static: ¾ end of scale
Oscillating: ¾ end of scale
Maximum: Full scale for a short period of time
Temperature limits:
Environment: -20+50°C
Fluid: 80°C
Range: -1+12 or -1+24 Bar
Scale: Bar/R22/R134a/R404a/R507
Antivibration fluid: Glycerin 99.8%
Sensor element: Bourdon tube (“C” form)
Overtemperature relief system: Upper plug
MATERIALS
Case: AISI 304 Stainless steel
Bourdon tube and moving parts: Cu Alloy
Threaded connection: Brass
Visor: Polycarbonate
Dial: White lacquered aluminum
Pointer: Black lacquered aluminum
Welding: Cu-Sn
Overtemperature relief plug: Neoprene